Get in Touch– For end-users with a valid active support contract (PSA or ASP), open a technical support case specifically asking for "the exclusive V31 build for M258 legacy project recovery."
Thousands of machines globally run on Modicon M238 and M258 controllers. SoMachine V3.1 is the native environment for these devices. somachine v31 exclusive
| Issue | Symptom | Workaround | |-------|---------|-------------| | HMI Web Viewer crashes | Closing a visualization window causes IDE to freeze | Disable "Hardware Acceleration" in Tools → Options → Visualization | | CANopen bus off error on M258 | Random bus errors with third-party drives | Insert a delay of 50ms before CANopen start in the PLC_Run routine | | Library download fails | "Version conflict: Lib 3.2.4 not found" | Manually copy the .library files from C:\ProgramData\Schneider Electric\SoMachine V31\Libraries | | USB dongle not recognized | "No valid license" despite dongle inserted | Reinstall the driver located in \Drivers\Sentinel on the installation media | – For end-users with a valid active support
For remote support, use the Gateway Management Console to set up Static Remote Connections, allowing technicians to diagnose controllers from different network segments. Hardware Compatibility: Hardware Compatibility: